Single-phase AC DC Measurements wide-range metering module

1.
Product introduction
1.1. Introduction:
JSY-MK-1031 is an integrated AC and DC measurement, which
can complete the power measurement, acquisition and data transmission.
Electrical parameter measurement products. Accurately
measure single-phase AC parameters (voltage, current, power, power factor,
frequency, electricity, etc.,
For details of the parameter list, please refer to the
electrical parameter register) and DC electrical parameters (voltage, current,
power, electricity). This product adopts
Using TTL level as the data communication interface, it is
completely isolated from the strong electric area, with small size, simple
interface, and measurement current range
It has the characteristics of wide range and high
flexibility, and can be flexibly embedded in various devices that need to
measure power consumption, which is very cost-effective.
JSY-MK-1031 single mutual inductance energy metering module
can be widely used in energy-saving renovation, electric power, communication,
railway, transportation,
In environmental protection, petrochemical, steel and other
industries, it is used to monitor the current and power consumption of AC
equipment.
1.2. Features
·
Collect single-phase AC
parameters, including voltage, current, power, factor, frequency, energy and
other electrical parameters;
·
Collect DC parameters,
including voltage, current, power, energy and other electrical parameters;
·
Using special measurement
chip, RMS measurement method, high measurement accuracy;
·
With 1 TTL communication
interface, compatible with 5V/3.3V interface;
·
The communication protocol
adopts standard Modbus-RTU, which has good compatibility and is convenient for
programming;
·
High isolation voltage,
withstand voltage up to DC3000V;
1.3, technical parameters
Data parameters:
1) Voltage range: 0~264V;
2) Current range: 10mA~20A;
3) Overload capacity: the current 1.2 times the range is
sustainable, and the voltage 1.5 times the range is not damaged;
4) Input impedance: voltage channel > 1 kΩ/V;
Communication interface:
1) Interface type: 1-way TTL communication interface,
compatible with 5V/3.3V;
2) Communication protocol: MODBUS-RTU protocol;
3) Data format: The default is "n,8,1",
"e,8,1", "o,8,1", "n,8,2" can be set;
4) Communication rate: The default is 9600bps, 4800bps,
19200bps can be set;
easurement output data:
Voltage, current, power, energy, power factor, frequency and
other electrical parameters, see the Modbus data register column surface;
Measurement accuracy:
Voltage, current, power, electricity: less than ±1.0%;
Isolation:
The power under test and the power supply are isolated from
each other; the isolation withstand voltage is 3000VDC;
Power:
DC single power supply 5V power supply, power consumption
10mA.
Working Environment:
1) Working temperature: -20~+70℃; Storage temperature: -40~+85℃;
2) Relative humidity: 5~95%, no condensation (under 40℃);
3) Altitude: 0 to 3000 meters;
4) Environment: no explosion, corrosive gas and conductive
dust, no significant shaking, vibration and shock;
5) Temperature drift: ≤100ppm/℃;
6) Installation method: PCB welding, the module plane size
is 39.5*21.0mm
7) Module size: 39.5*21.0*8.0mm
2.
Application
Product appearance
2.2, interface definition
2.2.1 Pin description:
Pin No | Feature | Functional
Description |
L | AC Mains Line
L | Measured
voltage live wire connection port |
N | AC Mains line
N | Neutral wire
connection port of measured voltage |
PF | Output | Active energy
check pulse output, the default state is low level output, generally do not
need to connect this pin, but keep it pin out
position |
TXD | Output | Module TTL
level sending pin |
RXD | Input | Module TTL
level receiving pin |
VCC | Power+ | Metering
module power supply pin, normal application range: 3.3V-5V |
GND | Power- | GND |
The live wire enters from the
"IN" short, and the "OUT" terminal outputs, connected to
the load;
2.3, application description
Please refer to the above diagram for correct wiring
according to the product specification and model. Make sure to disconnect all
signal sources before wiring to avoid
Danger and damage to equipment. After checking and
confirming that the wiring is correct, turn on the power supply to test.
After the power is turned on, the "indicator" is
always on, and the "indicator" flashes synchronously when the
communication data is transmitted during communication.
When the product leaves the factory, it is set to the
default configuration: address No. 1, baud rate 9600bps, data format
"n,8,1", transformation ratio is 1;
This product is adaptive to AC and DC signals, and the
default is AC module. When using this module to test DC signals, it is
necessary to use
The voltage above DC 5V activates the module as a DC module,
and the module needs to be powered on again when the signal source is changed.
Through the JSY-MK-1031 series product testing software we
provide, you can change the setting of product parameters and the general
testing of the product try.
2.4. Electric energy metering
function
Can provide single-phase voltage, current, power, power
factor, frequency, active energy and other parameters;
Note: The power data can store up to 42949672Kw/h of power,
and reset to zero after overflow.
3.
JSY-MK-1031 Modbus register list
Table 1: System configuration read parameter register
address and data communication table (function code 03H read, 10H write)
NO | Disc. | Register
Address | R/W | Specific
command |
1 | Address and
baudRate | 0004H | R/W | The default
value is 0106H; the default address is 01H, the default communication format
is 8, N, 1,9600bps illustrate: The high byte
8 bits are the address, 1~255; 0 is the broadcast address; The upper 2
bits of the low byte are the data format bits, If it is
"00", it means 10 bits without check, that is, "8, N, 1"; "01"
means 11 bits, even parity, that is, "8, E, 1"; "10"
means 11 bits, odd parity, that is, "8, 0, 1"; "11"
means 11 bits, no parity, 2 stop bits, namely "8, N, 2"; The lower
four bits of the low byte are the baud rate, 5-4800bps, 6-9600bps, 7-19200bps |
Table 2: System read-only parameter register address and communication
data table (function code 03H, read-only)
No | Disc. | Register
Address | R/W | Specific
command |
1 | Type 1 | 0000H | R | The value is
01031H |
2 | Type 2 | 0001H | R | Reserved |
3 | Voltage range | 0002H | R | The value is
250, which means 250V |
4 | Current range | 0003H | R | The value is
200, which means 20A |
Table 3: Measurement electrical parameter register and
communication data table (function code 03H read, 10H write)
NO | Disc | Address | R/W | Data Types
and Calculations Description |
1 | Voltage | 0048H | R | Unsigned
number, value=DATA/100, unit V |
2 | Current | 0049H 004AH | R | Unsigned
number, value = DATA/10000, unit A |
3 | Active Power | 004BH 004CH | R | Unsigned
number, value = DATA/100, unit is W |
4 | Total Active
Energy | 004DH 004EH | R/W | Unsigned
number, value = DATA/100, unit is kWh |
5 | Power Factor | 004FH | R | Unsigned
number, value=DATA/1000 |
6 | Frequency | 0050H |