Fluke 1625-2-KIT Advanced Geo Earth Ground Tester Kit

SKU: tar-st-Fluke 1625
In Stock
EGP 285,000.000 exc. vat
In Stock

Brand:Fluke
SKU: tar-st-Fluke 1625 Category: Tags: ,

Description

Fluke 1625-2-KIT Advanced Geo Earth Ground Tester Kit

ThisFluke 1625-2-KIT Advanced Geo Earth Ground Tester Kit Simpler, faster earth ground tests than ever before. With internal memory storage of up to 1500 records, users can have a faster setup made easy with the new color-coded wires that help eliminate mistakes.

Fluke 1625-2-KIT Advanced Geo Earth Ground Tester Kit

Features

  • One-button measurement concept
  • 3- and 4-pole earth ground measurement
  • 4-pole soil resistivity testing
  • Selective testing, no disconnection of ground conductor (1 clamp)
  • Stakeless testing, quick ground loop testing (2 clamps)
  • Measuring frequency 128 Hz

Applications

  • Oil and gas
  • Mining/mineral and metal processing
  • Process manufacturing – chemical processing
  • Utilities
  • Manufacturing: machinery, instrumentation, and appliances

How to Get Faster Three-Phase Power Measurements with Fluke Clamp Meters

Complete three-phase voltage and current measurements 50% faster! We’re confident in this because it’s been tested at customer sites. The new clamp meters from Fluke (models 377 FC & 378 FC) feature FieldSense™ technology where voltage and current can be measured simultaneously with the clamp jaw. Meaning, these clamp meters can be used to make sequential line-to-ground measurements and current measurements that result in calculated line-to-line voltage measurements and phase rotation information.

In this application note, we walk you through the old versus the new way of doing phase-to-phase measurements along with step-by-step instructions on how to make these measurements

Specifications

Temperature Range
Operating Temperature 14 to 122°F (-10 to 50°C)
Storage Temperature -22 to 140°F (-30 to 60°C)
Temperature Coefficient ±0.1% of reading/°C <18°C >28°C
Error Intrinsic: Refers to the reference temperature range and is guaranteed for one year
Operating: Refers to the operating temperature range and is guaranteed for one year
Climatic Class C1 (IEC 654-1), 23 to 115°F (-5 to 45°C), 5 to 95% RH
Protective Type IP56 for case, IP40 for battery door according to EN60529
Safety Protection by double and/or reinforced insulation maximum 50 V to earth. IEC61010-1: 300V CAT II, Pollution degree two
EMC (Emission Immunity) IEC61326-1: Portable
Quality System Developed, designed, and manufactured according to DIN ISO 9001
External Voltage V external, maximum = 24 V (dc, ac <400 Hz), measurement inhibited for higher values
V Ext Rejection >120 dB (16²⁄3, 50, 60, 400 Hz)
Measuring Time Typical six seconds
Maximum Overload 250 V rms (pertains to misuse)
Auxiliary Power 6 x 1.5 V Alkaline (type AA LR6)
Battery Life Span Typical >3000 measurements
RA 3-Pole Ground Resistance Measurement (IEC 1557-5)
Switch Position RA 3-pole
Resolution 0.001 to 10 Ω
Measuring Range 0.020 Ω to 19.99 kΩ
Accuracy ±(2% rdg + 3 d)
Operating Error ±(5% rdg + 3 d)
Measuring Principle: Current/Voltage Measurement
Measuring Voltage Vm = 48 V ac
Short-Circuit Current >50 mA
Measure Frequency 128 Hz
Probe Resistance (RS) Maximum 100 kΩ
Auxiliary Earth Electrode Resistance (RH) Maximum 100 kΩ
Additional Error from RH and RS RH[kΩ]RS[kΩ]/RA[Ω]0.2%
RA 4-Pole Ground Resistance Measurement (IEC 1557-5)
Switch Position RA 4-pole
Resolution 0.001 to 10 Ω
Measuring Range 0.020 Ω to 19.99 kΩ
Accuracy ±(2% rdg + 3 d)
Operating Error ±(5% rdg + 3 d)
Measuring Principle: Current/Voltage Measurement
Measuring Voltage Vm = 48 V ac
Short-Circuit Current >50 mA
Measure Frequency 128 Hz
Probe Resistance (RS + RES) Maximum 100 kΩ
Auxiliary Earth Electrode Resistance (RH) Maximum 100 kΩ
Additional Error from RH and RS RH[kΩ]RS[kΩ]/RA[Ω]0.2%
Monitoring of RS and RH with error indicator.
Automatic range selection.
RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp)
Switch Position RA 3-pole with clamp
Resolution 0.001 to 10 Ω
Measuring Range 0.020 Ω to 19.99 kΩ
Accuracy ±(7% rdg + 3 d)
Operating Error ±(10% rdg + 5 d)
Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
Measuring Voltage Vm = 48 V ac
Short-Circuit Current >50 mA
Measure Frequency 128 Hz
Probe Resistance (RS) Maximum 100 kΩ
Auxiliary Earth Electrode Resistance (RH) Maximum 100 kΩ
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp)
Switch Position RA 4-pole with clamp
Resolution 0.001 to 10 Ω
Measuring Range 0.020 Ω to 19.99 kΩ
Accuracy ±(7% rdg + 3 d)
Operating Error ±(10% rdg + 5 d)
Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
Measuring Voltage Vm = 48 V ac
Short-Circuit Current >50 mA
Measure Frequency 128 Hz
Probe Resistance (RS) Maximum 100 kΩ
Auxiliary Earth Electrode Resistance (RH) Maximum 100 kΩ
Monitoring of RS and RH with error indicator.
Automatic range selection.
Measurement is not performed if the current through the current clamp is too low.
Stakeless Ground Loop Measurement (2 Clamps)
Switch Position RA 4-pole 2 clamps
Resolution 0.001 to 10 Ω
Measuring Range 0.020 Ω to 19.99 kΩ
Accuracy ±(7% rdg + 3 d)
Operating Error ±(10% rdg + 5 d)
Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transformers
Measuring Voltage Vm = 48 V ac
Measure Frequency 128 Hz
Noise Current (IEXT) Maximum IEXT = 10 A (ac) (RA <20 Ω)
General Specifications
Display 1999 Digit LCD: Display with special symbols, digit height 25 mm, fluorescent backlight
User Interface Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button
Robust, Water and Dust Resistant Instrument is designed for tough environmental conditions (rubber protective cover, IP56)
Memory Internal memory storage up to 1500 records accessible via USB port
Dimensions 9.75 x 5.25 x 7.35″ (250 x 133 x 187 mm)
Weight 2.43 lbs (1.1 kg) including batteries
16.8 lbs (7.6 kg) included accessories and batteries in carrying case

 

Brand

Fluke

Fluke
Fluke

Reviews

There are no reviews yet.

Be the first to review “Fluke 1625-2-KIT Advanced Geo Earth Ground Tester Kit”

Refund Policy for UGE Electronics “Https://uge-one.com “

 

1. Returns and Refunds

Thank you for shopping at UGE Electronics “Https://uge-one.com “. If you are not entirely satisfied with your purchase, we’re here to help.

 

2. Eligibility for Refund

To be eligible for a refund, please make sure that:

– The item was purchased in the last 14 days.

– The item is in the original packaging.

– The item isn’t used or damaged.

 

3. How to Initiate a Refund

To initiate a refund, please contact our customer support at [[email protected]] or [01066552125]. Provide your order number and details about the product you would like to return.

 

4. Refund Processing Time

Once we receive your item, we will inspect it and notify you that we have received your returned item. We will immediately notify you on the status of your refund after inspecting the item.

If your return is approved, we will initiate a refund to your credit card (or original method of payment). You will receive the credit within a certain amount of days, depending on your card issuer’s policies.

 

5. Shipping Costs

Shipping costs are non-refundable. If you receive a refund, the cost of return shipping will be deducted from your refund.

 

6. Exchanges

If you wish to exchange an item, please contact our customer support. You will be responsible for the return shipping costs, and we will cover the shipping costs of the replacement item.

 

7. Damaged or Defective Items

If you received a damaged or defective product, please contact us immediately for assistance. We will work with you to resolve the issue promptly.

 

8. Contact Information

If you have any questions about our Refund Policy, please contact us at [[email protected]].

 

Important Note: This Return & Refund Policy is applied only for Orders invoiced VIA UGE Electronics, and regarding any Orders has been invoiced VIA any Other Vendor you can check the Return & Refund Policy of this Vendor VIA the Vendor Stroe Page, and it’s not our responsibility for any issue between you and the Vendor.

Product Enquiry

Please Login to make enquiry about this product