Description
2000 VA On-line double-conversion Uninterruptible Power Systems (UPS)
Advanced on-line protection for sensitive and critical loads.
Technical specifications :
TECHNOLOGY : On-line double-conversion
Rated voltage : 220 / 230 / 240 V
Voltage range 100% load : 176 ÷ 300 V
Voltage range 40% load : 100 ÷ 300 V
Rated frequency : 50 / 60 Hz
Total harmonic distortion (THDi) : <3.5%
Auto~detection of frequency : Yes
Protection : Resettable circuit breaker
——————————————————————————————————————————-
Rated voltage : 220 / 230 / 240 V
Voltage accuracy (battery mode) : ±1%
Power (VA/W) : 2000 / 1800
Total harmonic distortion (THDv) : <2% linear load / <5% non-linear load
Synchronised frequency : ±10%
Free running frequency : ±0.05 Hz
Frequency accuracy (battery mode) : ±0.05Hz
Compatibility with APFC loads : Yes
On-line performance : >89%÷92%
Eco-mode performance : >98%
Admissible overloads in battery mode : 105% constant / 130% for 10 s / 150% for 1 s
Admissible overloads in bypass mode : 130% constant / 180% for 60 s
Admissible overloads in-line mode : 105% constant / 130% for 60 s / 150% for 10 s / >150% for 300ms
——————————————————————————————————————————-
BYPASS :
Frequency range : ±5Hz
——————————————————————————————————————————-
Battery type : Pb-Ca sealed, AGM, maintenance-free
Charge type : I/U (constant current/constant voltage)
Recharge time : 4 hours to 90%
Battery test : Manual and/or automatic programmable
——————————————————————————————————————————-
COMMUNICATION :
Intelligent slot : Slot for SNMP/relays
Monitoring software : For Windows, Linux and Mac
——————————————————————————————————————————-
INDICATIONS :
OTHER FUNCTIONS :
Cold start (start-up from batteries) : Yes
Emergency stop (EPO) : Yes
——————————————————————————————————————————-
OPERATING MODES :
On-line double-conversion : Yes
Frequency converter (CVCF) : Yes (1)
——————————————————————————————————————————-
GENERAL :
Operating temperature : 0º C ÷ 40º C
Relative humidity : Up to 95%, non-condensing
Maxium operating altitude : 2,400 masl (power degradation up to 5,000 m)
Acoustic noise at 1 metre : ≤49 dB (100% load) / ≤41 dB (60% load)
——————————————————————————————————————————-
STANDARDS :
Electromagnetic compatibility (EMC) : EN 62040-2
Operation : VFI-SS-11 (EN-62040-3)
Corporate cerification : ISO 9001, ISO 14001, ISO 45001
——————————————————————————————————————————-
DIMENSIONS :
——————————————————————————————————————————-
WEIGHT :
————————————————————————————
Spain Brand / warranty : 2 Years
FOR DATASHEET AND MORE INFORMATIONS ABOUT PRODUCTS LIKE THIS PLEASE CLICKHERE.